The Control Volume
The whole PC case is considered the control volume. Air enters via the intake fans, combines with the internal air, and exits via the exhaust fans.
Assumption
The key assumption is that first there is steady state flow. The mass flow level and other properties at both inlet and outlet are constant over time. Another assumption is that there is no heat generated within the control volume. Only heat movement between the air and the internal element occurs. The third assumption is there are uniform inlet and outlet conditions. The air velocity and temperature are uniform across both inlet and outlet areas. Lastly, there is the assumption that there is no heat loss to the surroundings. The air moves away from every heat generated by a motherboard and fan.
Local Conditions:
The local average temperature will use the typical room temperature of (20oc), while the atmospheric pressure is (101,325 kPa) and therefore they form (T1) and (P1) respectively.
Minimum Required Fan Inlet Area
To calculate the minimum required fan inlet area, it is important to ensure the incoming air velocity constraint is achieved
Continuity equation is
Mass flow rate of air (m)= Density of air (p) x inlet air velocity (Vin) x inlet area (Ain)
M= (P x Vin x Ain)
Energy Balance- The first law of thermodynamics for an open system is
Q-W= m. (hout– hin)
Ideal Gas Law is
P= P/ R.T
For the air :
P is 101325 Pa
R = 287 J/kg
Tin= 20o C= 293k
Therefore, the density of air (p) is calculated as
P= (101325 / 287.293)
P= 1.204 kg/m3
For simplicity, applying cp for air is
H= (Cp x T)
Cp= 1005 J/Kg
Therefore
98= m. cp. (Tout – Tin)
Calculating for M
98= M x 1005. (305-293)
98 = m * 1005 (12)
M= 98/ 1005.12
= 0.0081 kg/ s
Minimum Required Fan Inlet Area:
Using the equation
0.0081= 1.204 x 1.5. Ain
Ain = (0.0081/ 1.204 x 1.5)
= 0.0045 m2
Converting Meter to centimetres
Ain = (0.0045 x 104)
= 45 cm 2